Part 2, Troubleshooting flowcharts – Generac Power Systems 8 kW LP User Manual

Page 42

Advertising
background image

Part 2

Page 40

AC GENERATORS

sEctioN 2.3

trouBlEsHootiNG floWcHarts

GOOD

GOOD

REPAIR OR REPLACE

IF RECONFIGURED TO LP GAS,
VERIFY THAT PROPER
PROCEDURE WAS FOLLOWED
(REFER TO SECTION 1.3)

TEST 18 - CHECK

VOLTAGE AND

FREQUENCY

UNDER LOAD

TEST 19 - CHECK

FOR OVERLOAD

CONDITION

TEST 15 - CHECK AND

ADJUST ENGINE

GOVERNOR

GO TO “PROBLEM 18 -

ENGINE STARTS HARD

AND RUNS

ROUGH/LACKS POWER”

SECTION 4.3

TEST 20 - CHECK

ENGINE CONDITION

NOT

OVERLOADED

GOOD

ENGINE

CONDITION

GOOD

DISCONTINUE

TESTING

LOOK FOR A SHORTED

CONDITION IN A

CONNECTED LOAD OR

IN ONE OF THE LOAD

CIRCUITS

REDUCE LOADS TO UNIT’S

RATED CAPACITY

BAD

REPAIR OR REPLACE

OVERLOADED

Problem 4 - Voltage and Frequency Drop Excessively When Loads Are Applied

UNITS WITH

V-TWIN

ENGINES

UNITS WITH

SINGLE

CYLINDER

ENGINES

TEST 7 - CHECK

STATOR AC

POWER WINDINGS

BOTH

LOW

GOOD

GOOD

BAD

GOOD

REPLACE

TEST 8 - TEST

BRUSHLESS

STATOR

TEST 10 - TEST

DPE WINDING

BAD

BAD

GOOD

TEST 16 - CHECK

STEPPER MOTOR

CONTROL

8/10 kW UNITS

12-20 kW UNITS