Transfer to standby, Part 3, Operational analysis – Generac Power Systems 8 kW LP User Manual

Page 66: Figure 5. transfer action to standby position, Page 64

Advertising
background image

tranSFer to StandBy

12 VDC is delivered to the transfer relay via Wire 15B and back to the circuit board via Wire 23. However, circuit
board action holds the Wire 23 circuit open and the transfer relay remains de-energized. On generator startup, an
“engine warm-up timer” on the generator circuit board starts timing. When that timer has timed out, circuit board
action completes the Wire 23 circuit to ground. The transfer relay then energizes, its normally open contacts
close, and standby source voltage is delivered to the standby closing coil via Wires E1 and E2, the transfer relay
(TR1) contacts, limit switch (SW3), Wire “B”, and a bridge rectifier. The standby closing coil energizes and the
main contacts actuate to their “Standby” side.

Page 64

NEUTRAL

CONNECTION

SWITCH

SW3

NO

C1

COM

SW2

VR1

NC

NC

COM

C2

VR2

NO

TR1

15B

23

1

7

4

7 9

3

6

9

F2

CIRCUIT 10

BLACK (MAIN 1)

CONTROL

TRANSFER

RED (MAIN 2)

NEUTRAL (WHITE)

NEUTRAL (WHITE)

23

0

F1

N2

N1

15B

23

BLACK

RED

N2

N1

15B

240VAC TO

TO GENERATOR

OUTPUT

PANEL

MAIN DISTRIBUTION

T1

T2

T1

T2

E2

E2

E2

E2

E1

E1

N1A

N1A

N2A

N2A

B

B

B

B

B

E1

E1

E1

N1A

N1A

N1A

15B

23

E1

E2

205

205

126

126

E2

N1A

N2A

N2A

A

N2A

240VAC

OUTPUT

GENERATOR

TS TO

CONTROL PANEL

A

B

SW1

LC

CIRCUIT 9

CIRCUIT 6

CIRCUIT 5

CIRCUIT 2

CIRCUIT 1

CIRCUIT 3

CIRCUIT 4

CIRCUIT 7

CIRCUIT 8

CIRCUIT 11

CIRCUIT 12

CIRCUIT 13

CIRCUIT 14

CIRCUIT 16

CIRCUIT 15

14 CIRCUIT LO

AD CENTER

12 CIRCUIT LO

AD CENTER

10 CIRCUIT LO

AD CENTER

8 CIRCUIT LO

AD CENTER

T1

T1

F3

0

WIRE

-

WIRE

BLK

+

RED

BC

0

16 CIRCUIT LO

AD CENTER

BC-BATTERY CHARGER

N-NEUTRAL

TR1-TRANSFER RELAY

SW2,SW3-LIMIT SWITCHES

TB1-TERMINAL STRIP

F1,F2,F3-5A, 600V FUSE

C1-UTILITY COIL & RECTIFIER

C2-GENERATOR COIL & RECTIFIER

SW1-AUTOMATIC TRANSFER SWITCH

(16 CIRCUIT SHOWN FOR REFERENCE ONLY)

LC-CIRCUIT BREAKER (LOADS)

LEGEND

SENSING

UTILITY

INSIDE

GROUND (GREEN)

GROUND (GREEN)

UTILITY

GENERATOR

GROUND

DC

Figure 5. Transfer Action to Standby Position

Part 3

TRANSFER SWITCH

sEctioN 3.2

oPEratioNal aNalYsis