18 enter new totalizer (flow total) values – Xylem 19 001 300 R2 Silent Storm VFD Pumping System OMRON Touch Screen Display Manual User Manual

Page 117

Advertising
background image

© 2013 Flowtronex

How Do I?

113

 

 

 

 

 

 

 

· N7 Misc. Control 3 Screen(PID Special Tuning Regs (dP in PSI):

 

– Enter the differential pressure (dP) for Response Reduction Above in register N7:123.

 

– Enter the differential pressure (dP) for Upper Threshold for Gain Enhancement in register

N7:126.

 

– Enter the unitless constant for Response Enhancements when dP above N7:126. in register

N7:127.

 

– Enter the differential pressure (dP) for Lower Threshold for Gain Enhancement in register

N7:128.

 

– Enter the Response Enhancements when dP above N7:128 in register N7:125.

 

– Optionally, press the Main Menu touch key to return to the Main Menu. (See also,

Main Menu

.)

 

– Optionally, press Back to return to the N Register Access screen.

 

– Press the up (▲) key to access the N7 Misc.Control 2 screen, or the down arrow

(▼) to advance to N7 Misc.Control 1.

 

 

Note:
Contact Flowtronex® Product Support for more information about the special use

registers.

 

 

2.18 Enter New Totalizer (Flow Total) Values

 

The password protected "totalizer" screen can be used to re-enter flow totals when data is lost for
some reason such as a power outage or installation of a new CPU in your pumping station. The
totalizer screen is accessed from the Register Access screen by pressing the N Register touch key.

Advertising