How Do I?
59
Note:
Flow setpoint to stop combo x are examples only. They are calculated based on
80% of the previous combo's maximum flow.
· Use the table below for these calculations and enter the values in GPM for Max Flow, Stop Combo
x registers N:23:1 to N:23:8 as needed.
Combo
Number
Pump
Size
Full Flow of
Previous combo
Flow Setpoint to
Stop Combo
1
20 HP
0 GPM
0.8 X 0 GPM = 0 GPM
2
50 HP
200 GPM
0.8 X 200 GPM = 160 GPM
3
75 HP
500 GPM
0.8 X 500 GPM = 400 GPM
4
75 HP and 50 HP
750 GPM
0.8 X 750 GPM = 600 GPM
6
75 HP, 50 HP, and 20HP
1250 GPM
0.8 X 1250 GPM = 1000 GPM
· Tap the value field next to any of these registers and the calculator/keypad pops-over the screen.
Enter or edit the value. (See also,
Calculator/Keypad
.)
· Optionally, press the Main Menu touch key to return to the Main Menu. (See also,
Main Menu
.)
· Optionally, press Back to return to the Register Access screen.
· Press the down arrow (▼) to display the VFD Bypass screen page 1.