How Do I?

59

 

 

 

 

 

 

 

 

Note:
Flow setpoint to stop combo x are examples only. They are calculated based on
80% of the previous combo's maximum flow.

 

 

· Use the table below for these calculations and enter the values in GPM for Max Flow, Stop Combo

x registers N:23:1 to N:23:8 as needed.

 

 

Combo
Number

 

Pump

Size

 

Full Flow of

Previous combo

 

Flow Setpoint to

Stop Combo

 

1

 

20 HP

 

0 GPM

 

0.8 X 0 GPM = 0 GPM

 

2

 

50 HP

 

200 GPM

 

0.8 X 200 GPM = 160 GPM

 

3

 

75 HP

 

500 GPM

 

0.8 X 500 GPM = 400 GPM

 

4

 

75 HP and 50 HP

 

750 GPM

 

0.8 X 750 GPM = 600 GPM

 

6

 

75 HP, 50 HP, and 20HP

 

1250 GPM

 

0.8 X 1250 GPM = 1000 GPM

 

 

· Tap the value field next to any of these registers and the calculator/keypad pops-over the screen.

Enter or edit the value. (See also,

Calculator/Keypad

.)

 

· Optionally, press the Main Menu touch key to return to the Main Menu. (See also,

Main Menu

.)

 

· Optionally, press Back to return to the Register Access screen.

 

· Press the down arrow (▼) to display the VFD Bypass screen page 1.