· Optionally, press the Main Menu touch key to return to the Main Menu. (See also,
Main Menu
.)
· Optionally, press Back to return to the previous screen, N Register Access screen.
· Press the Continue touch key to open the first Calibration screen.
2.13.1.1 Calibrating the Minimum (0) Pressure
Calibration page 1 shows the settings for Channel 0, the downstream transducer and Channel 1 the
upstream transducer. Values are shown in PSI. Use the following procedure to calibrate minimum or
zero pressure.
Follow these steps to calibrate minimum or zero pressure: