Xylem 19 001 300 R2 Silent Storm VFD Pumping System OMRON Touch Screen Display Manual User Manual

Page 41

Advertising
background image

© 2013 Flowtronex

How Do I?

37

 

 

 

 

 

 

 

The second Safety registers screen is devoted to optional safeties.

 

· N70:6 is the delay time for a Loss of Prime fault. In this case, a probe is placed in the suction

piping. The default value is 0 seconds.

 

· N70:7 is the delay time for a Low Inlet Pressure fault. Normally a pressure switch is installed in the

suction piping. The default value is 20 seconds.

 

· N70:8 is the delay time for a Flow Over-demand fault. The default value is 180 seconds.

 

· N71:8 is the flow at which a Flow Over-demand fault occurs. The default value is your total station

flow plus 20%.

 

· N70:9 is the delay time for a Filter Fault. The default value is 0 seconds.

 

· Optionally, press the Main Menu touch key to return to the Main Menu. (See also,

Main Menu

.)

 

· Optionally, press Back to return to the Register Access screen.

 

· Press the down arrow (▼) in the bottom right corner of the screen to display the Safety

registers page 3.