– 00000100 is Pump 2 and would be entered as 4 in B85:5.

 

– 00001000 is Pump 3 and would be entered as 8 in B85:5.

 

– 00010000 is Pump 4 and would be entered as 10 in B85:5.

 

– 00100000 is Pump 5 and would be entered as 20 in B85:5.

 

– 01000000 is Pump 6 and would be entered as 40 in B85:5.

 

– 10000000 is Pump 7 and would be entered as 80 in B85:5.

 

· B85:11 is the delay time for an individual booster pump High Discharge Pressure fault. The default

value is 60 seconds.

 

· B85:12 is the delay time for a booster pump start. The default value is 5 seconds.

 

· B85:13 is the delay time for an individual booster pump Low Discharge Pressure fault. The default

value is 300 seconds.

 

· B85:14 is the time delay until the booster pump stops is equipped with a limit switch. The default

value is 30 seconds.

 

· Tap the value next to any of these registers to open the calculator/keypad. Enter or edit the value.

(See also,

Calculator/Keypad

.)

 

· Optionally, press the Main Menu touch key to return to the Main Menu. (See also,

Main Menu

.)

 

· Optionally, press Back to return to the B Register Access.

 

· Press the down arrow (▼) to advance to the Booster Status page 2 screen.

 

 

 

The parameters shown on the Booster Status page 2 screen are read-only values.

 

· The main zone displays a 0 for Off, or a 1 for Run.

 

· The Booster Run is either ON or OFF.