© 2013 Flowtronex

50

Omron Touch-Screen Display

 

 

 

 

 

 

 

· N21:39 is the pressure above setpoint to stop combo 2. Default is 001 PSI.

 

· N21:40 is the delay time to stop combo 2. Default is 060 Sec.

 

· N21:41 is the pressure below setpoint to start combo 3+. Default is 015 PSI.

 

· N21:42 is the delay time to start combo 3+. Default is 010 Sec.

 

· N21:43 is the pressure above setpoint to stop combo 3+. Default is 001 PSI.

 

· N21:44 is the delay time to stop combo 3+. Default is 030 Sec.

 

· Tap the value field next to any of these registers and the calculator/keypad pops-over the screen.

Enter or edit the value. (See also,

Calculator/Keypad

.)

 

· Optionally, press the Main Menu touch key to return to the Main Menu. (See also,

Main Menu

.)

 

· Optionally, press Back to return to the Register Access screen.

 

· Press the up arrow (▲) in the bottom right corner of the screen to open the previous screen,

VFD Bypass page 1.

 

2.9 Define My Auto Lake Screen Parameters

 

You can access the Accessories screen and define your Automated Lake Screen (ALS) parameters by
pressing the Register Access touch key on the

Main Menu

and opening the Register Access screen.