Xylem 19 001 300 R2 Silent Storm VFD Pumping System OMRON Touch Screen Display Manual User Manual

Page 147

Advertising
background image

© 2013 Flowtronex

How Do I?

143

 

 

 

 

 

§ N61:1 set to 0 for Interchangeable Pumps (Interchange Groups screen).

 

§ T25:30 set to 15 to 20 seconds for Combo Overlap Time (Timer Access screen). This allows

pump 1 to switch to XL (across-the-line) and run for that length of time while the VFD for
Pump 2 ramps up. This is a tuned value to ensure minimal pressure drop during the switch.

 

§ N7:148 set to 3 for Jockey cycle "Jump to 0" combo to allow shutdown sequence to work

(More N7 Regs Misc. Control).

 

§ B3:2/4 set to 1 for Jockey Cycle On (More N7 Regs Misc. Control).

 

§ N7:149 set to 3 for the Combo Limit for HSS (More N7 Regs Misc. Control).

 

· B60:05 enables or disables a PM pump.

 

· Optionally, press the Main Menu touch key to return to the Main Menu. (See also,

Main Menu

.)

 

· Optionally, press Back to return to the previous screen

 

· Press the down arrow (▼) in the bottom right corner of the screen to display page 2 of the

B60 register.

 

 

 

· B60:08 defines an Auto Lake Screen. If this object is enabled, you will need to review your ALS

settings on the

Auto Lake Screen

,

Lake Fill

, and

Filter screens

.

 

· B60:10 and B60:11 enable and disable filters. Again, you will need to review your filter settings on

the "Auto Lake Screen, Lake Fill, and Filter" screens.

 

· B60:12 allows lake fill. Again, you will need to review your filter settings on the "Auto Lake Screen,

Lake Fill, and Filter" screens.

 

· B60:16 allows a Water Feature / Timed Pump. If this is enabled, you will need to review your

Timed Pump Data

screen.

 

· Optionally, press the Main Menu touch key to return to the Main Menu. (See also,

Main Menu

.)

Advertising