2.13.2.2 220B Flowmeter
Calibrating a single zone pulse flow sensor
A pulse type flow sensor uses a span and offset value based on flow meter spool pipe size to calibrate
it. See following table:
Pipe Size
(Schedule 40)
Span
(to be entered in N52:0)
Offset
(to be entered in N52:1)
3 inch
436
–06
4 inch
834
–23
6 inch
2157
–26
8 inch
4009
–28
10 inch
6453
–31
12 inch
9737
–36
14 inch
11610
–38
Access the Register Access screen by pressing the Register Access key on the
Main Menu
. The
calibration screens are accessed from the Register Access screen by pressing the N Register Menu
touch key.