How Do I?

81

 

 

 

 

 

 

 

· Optionally, press the Main Menu touch key to return to the Main Menu. (See also,

Main Menu

.)

 

· Optionally, press Back to return to the previous screen, Calibration page 4.

 

2.13.2.2 220B Flowmeter

 

Calibrating a single zone pulse flow sensor

 

A pulse type flow sensor uses a span and offset value based on flow meter spool pipe size to calibrate
it. See following table:

 

Pipe Size

(Schedule 40)

Span

(to be entered in N52:0)

Offset

(to be entered in N52:1)

3 inch

436

–06

4 inch

834

–23

6 inch

2157

–26

8 inch

4009

–28

10 inch

6453

–31

12 inch

9737

–36

14 inch

11610

–38

 

Access the Register Access screen by pressing the Register Access key on the

Main Menu

. The

calibration screens are accessed from the Register Access screen by pressing the N Register Menu
touch key.