Xylem 19 001 300 R2 Silent Storm VFD Pumping System OMRON Touch Screen Display Manual User Manual

Page 49

Advertising
background image

© 2013 Flowtronex

How Do I?

45

 

 

 

 

 

up.

 

· N20:4 defines the Lockout 1 maximum number of combos.

 

· N20:6 defines the Lockout 2 maximum number of combos.

 

· Tap the value field next to any of these registers and the calculator/keypad pops-over the screen..

(See also,

Calculator/Keypad

.)

 

· Optionally, press the Main Menu touch key to return to the Main Menu. (See also,

Main Menu

.)

 

· Optionally, press Back to return to the Register Access screen.

 

· Press the down arrow (▼) in the bottom right corner of the screen to open the next

screen, Lockout Registers page 2.

 

 

 

This screen allows you to set the start and stop times of each lockout period. All times are in 24 hour
military times. It also allows you to turn a timed pump on and off. A timed pump is normally a water
feature pump that needs to run at a certain time.

 

· Enter a time (in HHMM format) in N7:140 that is the Lockout 1 Start Time.

 

· Enter a time (in HHMM format) in N7:141 that is the Lockout 1 Stop Time.

 

· Enter a time (in HHMM format) in N7:142 that is the Lockout 2 Start Time.

 

· Enter a time (in HHMM format) in N7:143 that is the Lockout2 Stop Time.

 

· Enter a time (in HHMM format) in N7:144 that is the Time Pump Start Time.

 

· Enter a time (in HHMM format) in N7:145 that is the Time Pump Stop Time.

 

For example, if you wanted to run from 10 PM to 2 AM, you would set Lockout 1 start time to
2200, and Lockout 1 stop time would be set to 0200.

 

· Tap the value field next to any of these registers and the calculator/keypad pops-over the screen.