Omron Touch-Screen Display
1) Turn speed pot fully counter clockwise to its minimum setting.
2) View and average the value in Raw Data (:29), and enter in CH1 min (:69), and MinIn (:79).
3) Turn speed pot fully clockwise to its maximum setting.
4) View and average the value in Raw Data (:29), and enter in MaxIn (:89).
5) Enter 6400 in MinOut (:99).
6) Enter 32400 in MaxOut (:109).
Calibration is complete.
· Optionally, press the Main Menu touch key to return to the Main Menu. (See also,
Main Menu
.)
· Optionally, press Back to return to the N Register Access screen.
· Optionally, press the up (▲) or down arrow (▼) keys to access the other eight calibration
screens.
2.13.5 220B Flowmeter with Analog Transmitter
To set up a 220B Flow Meter with an Analog Transmitter, access the Register Access screen by
pressing the Register Access key on the
Main Menu
.
· Press the N Register Menu touch key on the Register Access screen to open the N Register
Access screen.