Xylem 19 001 300 R2 Silent Storm VFD Pumping System OMRON Touch Screen Display Manual User Manual
Page 47

© 2013 Flowtronex
How Do I?
43
· Enter a time in seconds in the T4:28 Pre field. Default delay time is 50 seconds for the Time until
dP (Differential Pressure) fault used on the Torpedo and scanner filters.
· Enter a time in seconds in the T4:40 Pre field. Default delay time is 3 seconds for the VFD run
feedback fault.
· Enter a time in seconds in the T25:30 Pre field. Default delay time is 1 seconds for the Combo
overlap during change.
· Tap the value field next to any of these registers and the calculator/keypad pops-over the screen.
Enter or edit the value. (See also,
Calculator/Keypad
.)
· Press the up arrow (▲) in the bottom right corner of the screen to open the previous
screen, Timer Access page 1.
2.7 Define Lockout, Timed Pump, and Well Pump Parameters
You can access the Lockout register screens and define your lockout parameters by pressing the
Register Access touch key on the
Main Menu
and opening the Register Access screen.