4 calibrate manual speed pot – Xylem 19 001 300 R2 Silent Storm VFD Pumping System OMRON Touch Screen Display Manual User Manual

Page 92

Advertising
background image

© 2013 Flowtronex

88

Omron Touch-Screen Display

 

 

 

 

 

 

 

Follow the following procedure to calibrate the VFD Pump RPM on channel 8:

 

1) Enter 6400 into Min Raw (:68) and MinIn (:78).

 

2) Enter 32400 into MaxIn (:88).

 

3) Enter 0 into MinOut (:98).

 

4) Enter Motor Nameplate RPM into MaxOut (:108). Normally 1765 or 3450 RPM.

 

· Optionally, press the Main Menu touch key to return to the Main Menu. (See also,

Main Menu

.)

 

· Optionally, press Back to return to the N Register Access screen

 

· Optionally, press the up (▲) or down arrow (▼) keys to access the other eight calibration
screens.

 

2.13.4 Calibrate Manual Speed Pot

 

Manual Speed Pot (Potentiometer) calibration is located on channel 9. Access the Register Access
screen by pressing the Register Access key on the

Main Menu

. The calibration screens are accessed

from the Register Access screen by pressing the N Register Menu touch key.