Follow the following procedure to calibrate the VFD Pump RPM on channel 8:
1) Enter 6400 into Min Raw (:68) and MinIn (:78).
2) Enter 32400 into MaxIn (:88).
3) Enter 0 into MinOut (:98).
4) Enter Motor Nameplate RPM into MaxOut (:108). Normally 1765 or 3450 RPM.
· Optionally, press the Main Menu touch key to return to the Main Menu. (See also,
Main Menu
.)
· Optionally, press Back to return to the N Register Access screen
· Optionally, press the up (▲) or down arrow (▼) keys to access the other eight calibration
screens.
2.13.4 Calibrate Manual Speed Pot
Manual Speed Pot (Potentiometer) calibration is located on channel 9. Access the Register Access
screen by pressing the Register Access key on the
Main Menu
. The calibration screens are accessed
from the Register Access screen by pressing the N Register Menu touch key.