Xylem 19 001 300 R2 Silent Storm VFD Pumping System OMRON Touch Screen Display Manual User Manual

Page 84

Advertising
background image

© 2013 Flowtronex

80

Omron Touch-Screen Display

 

 

 

 

Start at step 5. Your mA reading is 14 mA.
Subtracting 4 mA from this reading gives you an adjusted reading of 10 mA for step 6.
The max GPM @ 20 mA is 3900 GPM for step 7.

Dividing this value by 16 yields 243.75 GPM per mA for step 8.
Multiply the adjusted reading of 10 ma from step 6 by 243.75. Your answer is 2437.5 GPM.
Enter this value in MaxOut (:102).

Calibrating multiple zone pulse flow sensors connected to Krohne Flow meters

 

The calibration procedure is identical to the single zone procedure, with the exception that zone 1 is
now on channel 5 instead of channel 2, zone 2 is on channel 6, and zone 3 is on channel 7 (if

applicable). No further calibration is required.

 

Duplicate the single zone calibration procedure from earlier in this section, but ensure that you use the
correct channel.

 

 

 

· Optionally, press the Main Menu touch key to return to the Main Menu. (See also,

Main Menu

.)

 

· Optionally, press Back to return to the previous screen, Calibration page 2.

 

· Optionally, press the down arrow (▼) to advance to page 4 and 5 Calibration screens.

Advertising