138

Omron Touch-Screen Display

 

 

 

 

 

The following table gives you the bit sum to enter for each pump defined under registers N61:0 to
N61:3:

 

Pump #

Bit Sum

1

2

2

4

3

8

4

16

5

32

6

64

7

128

 

Example 1: You have three 75 HP main pumps, all of which can run on a VFD. You want all 3
pumps to be interchangeable and the pump with lowest hours should come on first.

You would set N61:0 to 14. This is the sum of the bits for the 3 pumps (2 + 4 + 8 from the table
above).

In this example, you would set your combos according to the following table:

 

 

Combo 1

Pump 1

Either Pump 1, 2, or 3 on the VFD

Same as above but with the pump with

Combo 2

Pumps 1& 2

 

 

 

Combo 3

Pumps 1, 2, & 3

the lowest hours set up as an
across-the-line lag pump

Same as above with the pump with the
highest hours set up as an

across-the-line lag pump.

 

 

Example 2: You have two 75 HP main pumps that can run on a VFD, or across-the-line. You
have two 60 HP main pumps that can run across-the-line only.

N61:0 is the first lead group. You would enter 6 for the first 2 pumps (2 + 4 from the table
above).

N61:1 is the second lead group. You would enter 24 for the pumps 3 and 4 (8 + 16 from the table
above).

In this example, you would set your combos according to the following table:

 

 

 

Combo 1

Pump 1

Either Pump 1 or 2 on the VFD

Either Pump 1 or 2 on the VFD with the

Combo 2

Pump 1& 2

non-VFD pump set to come on
across-the line pump