Xylem 19 001 300 R2 Silent Storm VFD Pumping System OMRON Touch Screen Display Manual User Manual
Page 99

© 2013 Flowtronex
How Do I?
95
·
Without An Analog Signal Generator
·
Multi Zone Pulse Flow Sensor Connected to an Analog Transmitter
2.13.5.1 Calibrating with an Analog Transmitter (Model 310)
An Analog Transmitter (such as the Model 310 normally used by Flowtronex®) converts the pulse
output of the 220B flow meter to a 4 to 20 mA analog signal. The Model 310 is calibrated at the factory
to provide specific full scale outputs based on pipe size. Use the following table to determine the
correct size.
Pipe Size
(Schedule 40)
Max GPM @ 20 mA
2 inch
200
2.5 inch
250
3 inch
400
4 inch"
800
6 inch"
1400
8 inch"
3000
10 inch"
5500
12 inch"
9000
14 inch"
11,500
There are two ways to calibrate the flow, with or without a 4-20 mA signal generator.
2.13.5.2 Calibration Procedure with a Signal Generator
Use the following procedure to calibrate a 220B Flowmeter with a Signal Generator. Information is
entered on the Calibration screen page 3.