Xylem 19 001 300 R2 Silent Storm VFD Pumping System OMRON Touch Screen Display Manual User Manual

Page 53

Advertising
background image

© 2013 Flowtronex

How Do I?

49

 

 

 

 

 

 

 

The values on the VFD Bypass screen page 1 are similar to but not identical to those used for normal

operation. They rarely would require changing. The default values are shown.

 

· N21:33 is the pressure below setpoint to start combo 1. Default is 005 PSI

 

· N21:34 is the delay time to start combo 1. Default is 000 Sec.

 

· N21:35 is the pressure above setpoint to stop combo 1. Default is 005 PSI

 

· N21:36 is the delay time to stop combo 1. Default is 005 Sec.

 

· N21:37 is the pressure below setpoint to start combo 2. Default is 012 PSI.

 

· N21:38 is the delay time to start combo 1. Default is 010 Sec.

 

· Tap the value field next to any of these registers and the calculator/keypad pops-over the screen.

Enter or edit the value. (See also,

Calculator/Keypad

.)

 

· Optionally, press the Main Menu touch key to return to the Main Menu. (See also,

Main Menu

.)

 

· Optionally, press Back to return to the Register Access screen.

 

· Press the down arrow (▼) in the bottom right corner of the screen to open the next screen,

VFD Bypass page 2.

Advertising