12 define my flow stop parameters – Xylem 19 001 300 R2 Silent Storm VFD Pumping System OMRON Touch Screen Display Manual User Manual

Page 61

Advertising
background image

© 2013 Flowtronex

How Do I?

57

 

 

 

 

 

 

 

· N80:15 is the number of chambers and is set at the factory. Do not change this value without

consulting Product Support at Flowtronex® .

 

· N80:21 is used if you place your filter switch in bypass mode. When in bypass mode, a minimum

wait of 10 minutes has to elapse before the filter flushes.

 

· N80:22 is also used if you place your filter switch in bypass mode. The filter will flush after 60

minutes if a dP (Differential Pressure) signal is not received.

 

· N80:24 is the alternate minimum time. This setting is only used for multiple scanner filters and is

the time between flushes for filters 1 and 2. (15 seconds is the default value).

 

· N70:9 is the filter fault timer. This is the delay time before the PLC recognizes a filter fault. ( 0

seconds is the default value).

 

· Tap the value field next to any of these registers and the calculator/keypad pops-over the screen.

Enter or edit the value. (See also,

Calculator/Keypad

.)

 

· Optionally, press the Main Menu touch key to return to the Main Menu. (See also,

Main Menu

.)

 

· Optionally, press Back to return to the

Register Access

screen.

 

· Press the up (▲) or down arrow (▼) key to display other Accessories parameters screens.

 

2.12 Define My Flow Stop Parameters

 

You can define your Flow Stop Presets by pressing the Register Access touch key on the

Main Menu

and opening the Register Access screen. The Flow Stop Preset screen is the third VFD Bypass screen
but you can use the N23 Flow Stop touch key to display this screen quickly.