11 define my filter parameters – Xylem 19 001 300 R2 Silent Storm VFD Pumping System OMRON Touch Screen Display Manual User Manual

Page 58

Advertising
background image

© 2013 Flowtronex

54

Omron Touch-Screen Display

 

 

 

 

 

 

 

· N80:31 is the delay time until Fill starts. This is normally set to 10 seconds.

 

· N80:32 is the delay time until Fill stops. This is also normally set to 10 seconds.

 

One other function is defined on this screen—Flow Activated PLC Relays. Depending on the
equipment connected to the relay, such as a fertigation relay, these two outputs can be used to set up
a minimum station flow required for operation.

 

· N84:0 is the Flow Activated PLC Relay 1. The default is 100 GPM.

 

· N84:1 is the another Flow Activated PLC Relay 1 that is rarely used. The default is 0 GPM.

 

· Tap the value field next to any of these registers and the calculator/keypad pops-over the screen.

Enter or edit the value. (See also,

Calculator/Keypad

.)

 

· Optionally, press the Main Menu touch key to return to the Main Menu. (See also,

Main Menu

.)

 

· Optionally, press Back to return to the

Register Access

screen.

 

· Press the up (▲) or down arrow (▼) key to display other Accessories parameters screens.

 

2.11 Define My Filter Parameters

 

You can access the Accessories screen and define your Filter parameters by pressing the Register
Access touch key on the

Main Menu

and opening the Register Access screen.