How Do I?

35

 

 

 

 

 

 

 

· Press the N70 & N71 Safeties touch key on the Register Access screen to display the first of three

Safety registers screens.

 

 

 

· N71:0 defines your Low Pressure Discharge fault. The recommended value to enter is 25 PSI.

 

For example, if your setpoint is 120 PSI and 25 PSI is entered in N71:0, a shutdown on low
pressure is initiated when the station pressure drops to 95 PSI.

 

 

Note:
The recommended value to enter is 25 PSI. This value is rarely changed except for a
booster application.