Electrical Connections continued

• Use circuit breakers on the incoming power lines.

• Grounding must be in accordance with NEC and CEC. If multiple AQUAVAR controllers are

installed near each other, each must be connected to ground. Take care to not form a ground
loop. Maintain a common ground.

• Wire must be made of copper and rated 60 / 75ºC (unless otherwise specified in the table

below). Refer to Tables 4, 5 and 6 for recommended wire gauges and temperature ratings.

Considerations for Control Wiring

Control wiring refers to the wires connected to the control terminal strip. Select control wiring
as follows:

• Shielded wire is recommended to prevent electrical noise interference from causing improper

operation or nuisance tripping.

• Use only UL™ recognized wire.

• Wire voltage rating must be at least 300 V for 230 Vac systems.

Installation Procedures

18

Model

Wire Size 208 Vac

Wire Size 230 Vac

Number

AWG

mm

2

AWG

mm

2

AV2V2S010D

14

2.5

14

2.5

AV2V2S020D

12

4.0

12

4.0

AV2V2S030D

10

6.0

10

6.0

AV2V2S050D

8

10.0

8

10.0

AV2V2S075D

6

16.0

6

16.0

AV2V2S100D

4

25.0

4

25.0

AV2V20010D

14

2.5

14

2.5

AV2V20020D

14

2.5

14

2.5

AV2V20030D

12

4.0

14

2.5

AV2V20050D

10

6.0

10

6.0

AV2V20070D

8

10.0

8

10.0

AV2V20100D

8

1

10.0

1

8

10.0

AV2V20150D

6

1

16.0

1

6

1

16.0

1

AV2V20200D

6

1

16.0

1

6

1

16.0

1

(1) Use wire rated 90ºC in an environment where the ambient temperature is greater than 40ºC (122ºF).

Table 4: Recommended Wire Gauges (230 Vac Models)