Technical Characteristics

85

Power and Current Ratings

(continued)

Motor Power

Input

Maximum Load

Maximum

Output Output Current (A)

Model

HP

kW

Voltage

Current (A)

Voltage

200/380 230/460/

Number

(Vac)

200/380 230/460/

(Vac)

Vac

575 Vac

Vac

575 Vac

AV2V20150D

15.0

11.0

Three-phase 200 52.1

46.4

0 to 230

48.3

42.0

AV2V20200D

20.0

15.0

to 230 ±15%

53.9

47.4

62.1

54.0

AV2V40010D

1.0

0.7

3.4

2.4

2.4

2.1

AV2V40020D

2.0

1.5

5.2

3.9

3.8

3.4

AV2V40030D

3.0

2.2

7.2

5.6

5.7

4.8

AV2V40050D

5.0

3.7

12.0

8.8

8.9

7.6

AV2V40075D

7.5

5.5

15.0

12.8

12.0

11.0

AV2V40100D

10.0

7.5

19.7

16.3

15.6

14.0

AV2V40150D

15.0

11.0

30.9

25.8

23.0

21.0

AV2V40200D

20.0

15.0

Three-phase

40.0

33.3

31.0

27.0

AV2V40250D

25.0

18.6

380 to 460

49.2

40.0

0 to 460

37.0

34.0

AV2V40300D

30.0

22.0

±15%

57.5

47.8

43.0

40.0

AV2V40400D

40.0

30.0

62.3

53.3

61.0

52.0

AV2C40500D

50.0

37.0

71.0

65.0

71.0

65.0

AV2C40600D

60.0

45.0

86.0

77.0

86.0

77.0

AV2C40750D

75.0

55.0

105.0

96.0

105.0

96.0

AV2V40500D

50.0

37.3

69.0

58.0

73.0

65.0

AV2V40600D

60.0

44.7

82.0

68.8

87.0

77.0

AV2V40750D

75.0

56.0

98.3

82.2

105.0

96.0

AV2V50010D

1.0

0.7

2.0

1.7

AV2V50020D

2.0

1.5

3.6

2.7

AV2V50030D

3.0

2.2

5.0

3.9

AV2V50050D

5.0

3.7

7.6

6.1

AV2V50075D

7.5

5.5

10.4

9.0

AV2V50100D

10.0

7.5

14.1

11.0

AV2V50150D

15.0

10.0

Three-phase

20.8

0 to 575

17.0

AV2V50200D

20.0

15.0

575 ±15%

27.8

22.0

AV2V50250D

25.0

18.6

33.4

27.0

AV2V50300D

30.0

22.0

39.1

32.0

AV2V50400D

40.0

30.0

52.0

41.0

AV2C50500D

50.0

37.0

52.0

52.0

AV2C50600D

60.0

45.0

62.0

62.0

AV2C50750D

75.0

55.0

77.0

77.0

(1) Consult factory.