Programming, V. single pump - level control applications, Screen – Xylem IM131R01 AQUAVAR AV II User Manual

Page 44

Advertising
background image

V. Single Pump - Level Control Applications

For drainage applications using a surface pump, the transducer is typically needed to measure pres-
sure on the suction line. As the catch basin or tank empties, the pressure will decrease, and the
pump needs to slow down and eventually stop. This is the opposite way the AQUAVAR II controller
would usually respond. To change to suction side measurement:

1. On the main menu, enter the PSI value of the

liquid at the LOWEST level you want to main-
tain. For example, you may want to leave 3-4
feet of water in a tank which is equal to 2-3
PSI.

2. From the main menu, hold down the

key for 2-3 seconds until the screen changes
to:

• Enter 66 by pressing the key.

3. Use the key to scroll to:

• Use the key to change to inverse.

4. Briefly press the key until the screen:

5. Hold down the at the same time until:

The display will automatically return to the
main menu.

In operation, the pump will start wherever the suc-
tion side pressure is above the set point and slow
down and stop when the suction pressure comes
down to the set point and stays there.

43

Programming

For discharge level control, the programming operation is the same as a constant dis-
charge pressure system.

Note

REQUIRED VALUE - PSI

Screen

*

*

*

PASSWORD 2000

0066

REGULATION MODE - NORMAL

REGULATION MODE - INVERSE

SAVE ??? SAVED

SAVE ??? +