Programming, Vii. setting a second fixed required value – Xylem IM131R01 AQUAVAR AV II User Manual

Page 47

Advertising
background image

VII. Setting A Second Fixed Required Value

The AQUAVAR II controller can also be used in applications where the required value changes. As an
example, a single pump system might be used to supply both water supply and irrigation needs on
a farm. When the irrigation system is used, the pressure which needs to be maintained is higher
than the pressure for normal water supply. The AQUAVAR II gives you the ability to program in this
higher set point and to automatically change to it when the irrigation system turns on, and change
back when it turns off.

Electrical
Wiring for the switch to change between one set point and the other is shown below. This could be
a normal switch or a timer for automatic operation. Wire the switch to X1-14 and X1-10 (ground).
When the switch is open, set point 1 is used. Closing the switch activates set point 2.

*Refer to Appendix B for explanation of terminals.

Programming

46

14

13

12

11

10

9

8

7

6

5

4

3

2

1

Digital Input

X1

Voltage signal input 0..10V or 2..10V

Current signal input 4..20mA

Analogue signal output 0-10V

Ground

Motor thermoswitch or PTC

Low Water

External on/off

+15 VDC max. 100mA

Actual value signal input 4-20mA

Screen

External switch

between required

value 1 and

required value 2