Table 13: AQUAVAR Electrical Fault Codes

(continued)

Fault Code

Fault Name

Possible Cause(s)

How to Recover

04

TSP 24V Supply

Overloaded +24 Vdc supply.

Check the loading on the +24
Vdc supply and remove any
excess load.

05

DC Volt Calibr

DC voltage is outside of normal • Check line voltage.
limits on power-up. This may

• Check the Supply Voltage

be caused by:

parameter.

• High or low line voltage.
• Supply voltage parameter

incorrectly set.

06

IOC Trip

Output short-circuit. May also

• Check motor wiring.

be caused by a ground fault

• Extend acceleration ramp.

(see Fault Code 11 below).

• Reduce boost.
• Check for ground faults.

07

Ext Flt/Warning

The configured input sensed an Investigate why the external fault

(Fault)

external fault.

occurred and correct.

09

Inter-Proc Comm

Loss of communication with

Reset the drive by pressing the

the control terminal strip.

Stop key for more than 1 second.
If problem persists, consult the
factory.

11

Ground Fault

The drive detected that the sum • Check motor wiring.
of the motor phases’ current is

• Check for and remove any

not zero. This may be caused

capacitive load.

by insulation failure in the

• Check the motor and cabling

motor or the cables.

for shorts to ground.

12

Input Phase Loss

Current measurement detected

Check input power cables.

an input phase with no current.

13

Overvoltage

The voltage of the internal DC-

• Adjust deceleration time.

link has exceeded 135% of the

• Add dynamic braking module.

Nominal voltage. This may be
caused by incorrect deceleration
time or high overvoltage spikes
on line.

14

Under Voltage

The DC bus voltage fell below

Reset fault and attempt to restart.

65% of the nominal voltage. This Check the line for proper supply.
may be due to line supply failure

If fault persists, an internal fault

or internal failure of the drive.

has occurred; contact the factory.

Repair of Faults and Errors

71