Repair of faults and errors – Xylem IM131R01 AQUAVAR AV II User Manual

Page 73

Advertising
background image

Repair of Faults and Errors

72

Table 13: AQUAVAR Electrical Fault Codes

(continued)

Fault Code

Fault Name

Possible Cause(s)

How to Recover

16

Motor Over Temp The drive’s motor temperature

Decrease motor loading. If the

(Fault)

model detected motor

motor is not overheated, check

overheating severe enough to

the temperature model

cause a fault.

parameters.

17

Output Fault

The output sensor detected

• Check motor wiring.

an error.

• Check for and remove any

capacitive load.

• Check the motor and cabling

for shorts to ground.

18

Overcurrent

The drive has measured

• Check the load, motor size,

excessive current in the motor

and cables.

output. This may be caused by: • Review the settings for
• Sudden, heavy load increase.

acceleration and deceleration

• Short circuit in the motor

times.

cables.

• Unsuitable motor.

19

Drive Over Temp

Temperature of the drive’s

• Check the air flow.

heatsink is too high.

• Check that the heatsink is not

clogged.

• Check the ambient

temperature.

• Check that the switching

frequency is not too high
compared to ambient
temperature and load.

20

Motor Overload

Excessive load on the motor

Check the motor and load.

(for example, a jammed load.)

21

Drive Under Temp • Temperature of the drive’s

• Increase the ambient

heatsink is below 0ºC (32ºF).

temperature.

• Ribbon cable not correctly

• Ensure that the ribbon cable is

seated between the power

correctly seated.

and control boards.

22

Motor Stall

The motor’s stall protection

Check the motor.

(Fault)

sensed a stall severe enough
to cause a fault.