Phase Imbalance

Phase voltage imbalance of the input AC source can cause unbalanced currents and excessive
heat in the drive’s input rectifier diodes and DC bus capacitors. Phase imbalance can also damage
motors running directly across the line.

Step 9 - Terminals Found on the Power Board

Description of the Terminals

Diagram 4 shows the power terminals for the AQUAVAR controller. Table 8 describes the terminals.

Table 8: Description of Power Terminals

Terminal

Description

TB1 Terminal Group

GND

Earth ground.

L1/R

These terminals are the line connections for three-phase models. (Single-phase

L2/S

models will only have the L1/R terminal, with the other two terminals being

L3/T

replaced by a terminal labeled N.)

T1/U

T2/V

These terminals are for motor connections.

T3W

Installation Procedures

21

CAUTION!

EQUIPMENT DAMAGE HAZARD - NEVER USE POWER-FACTOR CORRECTION
CAPACITORS ON MOTOR TERMINALS T1/U, T2/V OR T3/W. DOING SO WILL
DAMAGE THE SEMICONDUCTORS. FAILURE TO OBSERVE THIS INSTRUC-
TION CAN RESULT IN INJURY OR EQUIPMENT DAMAGE.

GND

L1/R

L2/S

L3/T

B–

B

+ DB

T1/U

T2/V

T3/W

GND

Diagram 4: AQUAVAR Controller Power Terminals