Programming – Xylem IM131R01 AQUAVAR AV II User Manual

Page 36

Advertising
background image

2. Press the key until you reach the number

66. You will now be able to access all of the
alternate menus for all AQUAVAR controller
optional controls.

3. Press

to advance the display to the next

window:
The jog mode is very useful because it allows
you to check on the actual outgoing frequency
and system pressure. By pressing either or

the controller changes to manual, and you

can change the frequency to set any constant
speed. The Aquavar returns to normal auto-
matic operation when you leave the jog mode
window.

4. Continue to briefly touch the

key to

scroll past all of the windows and submenus
until you reach:

5. Hold the

key down for 2-3 seconds

until the display changes to:

6. Set the minimum pressure the system is

allowed to maintain before shutting down. For
example, if the set point for the system is 50
PSI, and the operator will allow anything
above 41 PSI, then the conveyor limit would
be set at 40 PSI. This function can also be turned
off by pressing until “disabled” is shown.

To set timed protection:

7. Delay Time Enter the amount of

time that the pump is allowed to run at
maximum frequency after pressure begins
to drop below the conveyor limit. This should never occur if the system has been
properly sized and there are no leaks in the system. Note: This delay time is also
applied to low suction pressure switch, on terminal X1, 6 and 7.

35

Programming

SET CONVEYOR LIMIT

40 PSI

DELAY TIME

*

*

SUBMENU ERRORS

CONVEYOR LIMIT

Disabled

*

0066

JOG MODE