Repair of Faults and Errors

Table 13: AQUAVAR Electrical Fault Codes

(continued)

Fault Code

Fault Name

Possible Cause(s)

How to Recover

40

Loss of Keypad

Communication with the keypad Investigate and correct

is lost while keypad control is

communication problem.

active.

41

Ext Flt/Warning

The configured input sensed an

Investigate why the external fault

(Warning)

external fault.

42

Ser Lnk TimeOut

The watchdog timer for Modbus Reset and restore serial link

serial communications timed out. communications.

43

DI Logic Not Set

DI active logic is not set.

Set DI active logic via Active

Logic parameter.

44

DI Logic Changed Consult factory.

Consult factory.

50

Fan Fault

The cooling fan on the drive’s

Remove obstruction.

enclosure is drawing too much

current, which may indicate that Replace fan.

the fan is jammed or has failed.

51

Fan Warning

The cooling fan on the drive’s

Remove obstruction.

enclosure is drawing excessive

current, but not enough to

generate a fault. This may

indicate that the fan is jammed.

52

Motor Over Temp The drive’s motor temperature

Decrease motor loading. If the

(Warning)

model detected motor

motor is not overheated, check

overheating, but not severe

the temperature model

enough to generate a fault.

parameters.

53

Motor Stall

The motor’s stall protection

Check the motor.

(Warning)

sensed a stall, but not severe

enough to cause a fault.

54

Motor Underload

The load on the motor is

Check the motor and load.

(Warning)

insufficient, but not so low that

a fault occurs.

55

DeviceNet

No DeviceNet communication

Reset and restore DeviceNet

Timeout (Fault)

has occurred in the specified

communication. See the

amount of time, and a fault

DeviceNet manual for further

occurs.

information.

56

DeviceNet

No DeviceNet communication

Reset and restore DeviceNet

Timeout

has occurred in the specified

communication. See the

(Warning)

amount of time, and a warning DeviceNet manual for further

occurs.

information.

57

Network Ext Fault The external communication

Reset and restore DeviceNet

network delivered a command

communication.

to the drive that is forcing a

system-wide error.

58

Ser Lnk TimeOut

The programmed value of

Reset and restore serial link

(Warning)

parameter Comm Timeout

communications.

was exceeded.

74

Advertising