Repair of Faults and Errors
Table 13: AQUAVAR Electrical Fault Codes
(continued)
Fault Code
Fault Name
Possible Cause(s)
How to Recover
40
Loss of Keypad
Communication with the keypad Investigate and correct
is lost while keypad control is
communication problem.
active.
41
Ext Flt/Warning
The configured input sensed an
Investigate why the external fault
(Warning)
external fault.
42
Ser Lnk TimeOut
The watchdog timer for Modbus Reset and restore serial link
serial communications timed out. communications.
43
DI Logic Not Set
DI active logic is not set.
Set DI active logic via Active
Logic parameter.
44
DI Logic Changed Consult factory.
Consult factory.
50
Fan Fault
The cooling fan on the drive’s
Remove obstruction.
enclosure is drawing too much
current, which may indicate that Replace fan.
the fan is jammed or has failed.
51
Fan Warning
The cooling fan on the drive’s
Remove obstruction.
enclosure is drawing excessive
current, but not enough to
generate a fault. This may
indicate that the fan is jammed.
52
Motor Over Temp The drive’s motor temperature
Decrease motor loading. If the
(Warning)
model detected motor
motor is not overheated, check
overheating, but not severe
the temperature model
enough to generate a fault.
parameters.
53
Motor Stall
The motor’s stall protection
Check the motor.
(Warning)
sensed a stall, but not severe
enough to cause a fault.
54
Motor Underload
The load on the motor is
Check the motor and load.
(Warning)
insufficient, but not so low that
a fault occurs.
55
DeviceNet
No DeviceNet communication
Reset and restore DeviceNet
Timeout (Fault)
has occurred in the specified
communication. See the
amount of time, and a fault
DeviceNet manual for further
occurs.
information.
56
DeviceNet
No DeviceNet communication
Reset and restore DeviceNet
Timeout
has occurred in the specified
communication. See the
(Warning)
amount of time, and a warning DeviceNet manual for further
occurs.
information.
57
Network Ext Fault The external communication
Reset and restore DeviceNet
network delivered a command
communication.
to the drive that is forcing a
system-wide error.
58
Ser Lnk TimeOut
The programmed value of
Reset and restore serial link
(Warning)
parameter Comm Timeout
communications.
was exceeded.
74