IX. Multiple Pump Constant Pressure and System Curve

Compensation

When two, three, or four AQUAVAR II controller controlled pumps are connected in a system, they can
be programmed to work together to maintain system pressure up to the maximum flow rate of all
pumps combined. As the first pump reaches its maximum speed and flow, the second pump will
automatically turn on (and so on). In addition, the sequence of the pump that will run first (lead
pump) can be automatically varied to reduce premature wear on any one pump in the system.

1. Refer to the section The Main Menu - Setting One Pump Constant Pressure.

Follow steps 1 through 6, then continue with step 2 below.

Instructions

2. From the main menu, hold down on

the key for 2-3 seconds until the
display changes to:

• Use to enter the number:

3. Mode: Multicontroller This setting allows

the AQUAVAR II controller units to communicate
with each other in a multi-pump system.

• Use the

key to scroll through the

screens to reach:

• Use the

to change the setting to:

4. Advance to the next screen:

53

Programming

*

PASSWORD 0000

0066

Screen

MODE CONTROLLER

MODE: MULTICONTROLLER

SUBMENU SEQ CONTROL

*

Other possibilities are Synchronous Controller described later in this section and
Actuator which shuts off the internal controller and allows the

AQUAVAR II to function

as a standard VFD. This can be from external input (actuator) or manual control (actua-
tor local). This is described further in operator custom features and displays.