Installation procedures – Xylem IM131R01 AQUAVAR AV II User Manual

Page 23

Advertising
background image

Electrical Connections continued

Typical Power Connections

Diagram 5 shows the terminal connections for line power and motor output. See Step 8 for input
line requirements.

Note that when testing for a ground fault, do not short any motor lead (T1/U, T2/V or T3/W) back
to an input phase (L1/R, L2/S or L3/T).

As shown in Diagram 5, it is necessary to provide fuses and a disconnect switch for the input AC
line in accordance with all applicable electrical codes. The drive is able to withstand a 110% over
load for 60 s. For maximum protection of the drive, use the fuses listed in Tables 9, 10 and 11
found below and on the next page. The recommended supplier is Bussman.

Table 9: Recommended Fuses (230 Vac Models)

Fuse Size 208 Vac

Fuse Size 230 Vac

Model Number

JJS/JJN

1

JJS/JJN

1

AV2V2S010D

15

10

AV2V2S020D

20

20

AV2V2S030D

30

30

AV2V2S050D

45

45

AV2V2S075D

60

60

AV2V2S100D

80

80

AV2V20010D

10

6

AV2V20020D

15

10

AV2V20030D

20

15

AV2V20050D

30

25

AV2V20075D

40

35

AV2V20100D

50

40

AV2V20150D

70

60

AV2V20200D

70

60

(1) For sizes up to and including 30 A, KTK fuses may be substituted.

Installation Procedures

22

AV2V Drive

Motor

Fuses

Disconnect

Switch

Three-Phase

AC P

ower

L1/R

L2/S

L3/T

T1/U

T2/V

T3/W

GND

GND

Diagram 5: Connections for Power Wiring