Electrical Connections continued
Typical Power Connections
Diagram 5 shows the terminal connections for line power and motor output. See Step 8 for input
line requirements.
Note that when testing for a ground fault, do not short any motor lead (T1/U, T2/V or T3/W) back
to an input phase (L1/R, L2/S or L3/T).
As shown in Diagram 5, it is necessary to provide fuses and a disconnect switch for the input AC
line in accordance with all applicable electrical codes. The drive is able to withstand a 110% over
load for 60 s. For maximum protection of the drive, use the fuses listed in Tables 9, 10 and 11
found below and on the next page. The recommended supplier is Bussman.
Table 9: Recommended Fuses (230 Vac Models)
Fuse Size 208 Vac
Fuse Size 230 Vac
Model Number
JJS/JJN
1
JJS/JJN
1
AV2V2S010D
15
10
AV2V2S020D
20
20
AV2V2S030D
30
30
AV2V2S050D
45
45
AV2V2S075D
60
60
AV2V2S100D
80
80
AV2V20010D
10
6
AV2V20020D
15
10
AV2V20030D
20
15
AV2V20050D
30
25
AV2V20075D
40
35
AV2V20100D
50
40
AV2V20150D
70
60
AV2V20200D
70
60
(1) For sizes up to and including 30 A, KTK fuses may be substituted.
Installation Procedures
22
AV2V Drive
Motor
Fuses
Disconnect
Switch
Three-Phase
AC P
ower
L1/R
L2/S
L3/T
T1/U
T2/V
T3/W
GND
GND
Diagram 5: Connections for Power Wiring