Lack of Water
This error message will be displayed when a switch has indicated that the incoming water pressure
or water level in a suction tank falls below the required NPSH of the pump. If suction conditions
appear to be correct, check the pressure switch or float switch to make sure it is operating proper-
ly. When the suction conditions have returned to normal, the pump will restart automatically. This
message will also appear if terminals 6 and 7 on terminal block X1 are not bridged.
Conveyor Control (Value Range Control)
The drive is not able to obtain the minimum required value set in the conveyor limit setting. Look
for potential reasons for the low signal or lower the “CONVEYOR CONTROL” or increase the
“DELAY TIME” settings.
Error 1 through Error 8
These are program errors within the AQUAVAR II controller control system. If one of these errors
occurs, turn the unit off for at least 30 seconds and then back on. If the error is displayed again,
contact your Goulds Pumps AQUAVAR II distributor with an exact description of the fault.

Error 1 Eprom Error
Error 2 Security Software Protection Error
Error 4 Keyboard Error, check pushbuttons for proper actuation, or buttons may be held

down by the cover being on too tight.

Error 5 Eprom Error
Error 6 Watchdog Error
Error 7 Processor Pulse Error (Failure of oscillator for processor)
Error 8 Invalid Processor Command Error, power wires and motor leads may be too close

to the control board or communication ribbon.

Pressure Sensor Error
The pressure or flow sensor is out of order, not connected properly, not zeroed properly, or the
cable is damaged. Check the sensor and zero object and then turn the unit back on.
Actual Value Sensor Error (Act. Val. Sens. Error)
The AQUAVAR does not receive a 4-20 mA signal from transmitter. Check transducer wiring, connec-
tions and for the 4-20 mA signal. Once corrected, turn power off for at least 30 seconds to restart.
Inverter Error
A problem or error has occured in the internal drive. Check the active fault history on internal
display, page 70. Press SHIFT + ENTER keys to read fault history and fault codes, Diagram 20,
page 70, for list of fault codes.

69

DISCONNECT POWER FROM THE AQUAVAR CONTROLLER BEFORE CONNECT-
ING THE FAULTS TO AVOID POTENTIAL FOR AUTOMATIC PUMP RESTART.

WARNING

WARNING

Hazardous
voltage

Repair of Faults and Errors