G. Use the up or down arrow keys to change the parameter’s value to the desired value.
H. Press ENTER to save the new value. (If you do not wish to save the new value, press

SHIFT.)

I. The new value is stored, or discarded, and then the list of parameters is shown.
J. You may now select another parameter or return to the Operate mode by pressing

the PROG key.

6. You need to set up the AQUAVAR controller for the type of pump motor you are using. Press the

PROG key to display the list of functions. Use the up or down arrow to scroll to the NOM MTR
CURRENT parameter.

7. Press the ENTER key and then the up and down arrows to change the value to match the SFA

(Service Factor Amps) shown on your pump motor data plate. Once complete, press ENTER
again. (Maximum S.F. amps is 10% above nominal controller output amps.) See pages 86 and 87.

8. Scroll to the NOM MTR VOLTAGE parameter and press ENTER. Use the up and down arrows

to enter the voltage on the motor nameplate. For multi-voltage motors, select the voltage to
match your line voltage. Press ENTER to save the value.

9. Scroll to the NOM MTR FREQ parameter and press ENTER. Use the up and down arrows to

enter the maximum frequency for the motor design you are using. This would be either 50 Hz
or 60 Hz. Press ENTER to save the value.

10. Scroll to the NOM MTR RPM parameter and press ENTER. Use the up and down arrows to

enter the maximum RPM for the motor you are using. THis can be found on the motor
nameplates. Press ENTER to save the value.

11. Scroll to the SUPPLY VOLTAGE parameter. Press ENTER and use the up and down arrows to

put in the voltage available on the input line. Press ENTER to save the value.

12. Scroll to the Language parameter. Press the ENTER key and use the up and down arrows to

change the display language if needed. Press ENTER to save the value.

13. Press the PROG key again, close the panel door and go back to the main AQUAVAR display.

14. Press the down arrow key

The next display will be:

15. Press the up arrow

to turn on the AQUAVAR II controller.

16. Open the discharge valve slowly until the pump starts.

Observe the rotation of the pump shaft or motor fan.

17. Close the discharge valve.

18. Press the down arrow

to turn off the AQUAVAR II controller.

Installation Procedures

(continued)

30

INVERTER STOP - ON -> START

RUN LIGHT ON

Advertising