Programming – Xylem IM131R01 AQUAVAR AV II User Manual

Page 46

Advertising
background image

Programming

45

At the status window, hold the key until you
reach the password screen. Enter the password.

Use the key to advance to:

Use the and to change to the desired minimum
frequency (Example 35 Hz).

Use the key to advance to:

Use the and arrow keys to change to:
This allows the AQUAVAR II to go down to the select-
ed minimum frequency but not below it.

Use the key to advance to:

Use the and keys to enter the number of sec-
onds the AQUAVAR II will run at minimum speed
before it shuts off when there is no demand.

Advance to the same window and save all settings.

PASSWORD 0066

*

MINIMUM FREQUENCY

0 Hz

MINIMUM FREQUENCY

35 Hz

*

*

CONFIG. FMIN

F -> FMIN

CONFIG. FMIN

F => 0

In the setting f -> Fmin, the AQUAVAR II will only run between minimum frequency
and maximum frequency. Automatic shut off is not possible, but manual shut off is
possible with external on/off connected at X1/4 and X1/5.

Note

STOP - DELAY FMIN

OS

*

STOP - DELAY FMIN

10

SAVE ??? +