Single Pump Constant Flow continued

5. Use the to change the units to GPM if you are using a flow sensor or % if you are using

the orifice plate.

6. Hold down the key until the screen:

7. Hold down the key until the screen:

8. Enter either 37 psi for orifice plate application or the maximum flow range of your flow

sensor in gpm.

9. Hold down the at the same time until

The display will automatically return to the
main menu.

10. Advance to the screen:

11. Use either

to enter the flow you want

to maintain on the AQUAVAR II controller
(see example). For orifice plate applications,
use the table below to set the required %.

Select orifice size from the following chart. Select the orifice by the maximum flow of the
pump.

Based on the maximum flow shown for the orifice selected, calculate the percent of maximum flow
you want to maintain. For example, to maintain a flow of 20 GPM with a #1 orifice, select 57% (20
÷ 35).

42

Programming

Screen

REQUIRED VALUE

REQUIRED VALUE 35 GPM

SAVE ??? SAVED

Nominal Pipe

Flow Range

Orifice

Size

GPM

1

1"

12-35

2

1"

18-52

3

1

1

/

2

"

20-62

4

1

1

/

2

"

32-90

5

2

1

/

2

"

35-105

*

GPM

*

NORMALIZE 20 mA = 40 GPM

Nominal Pipe

Flow Range

Orifice

Size

GPM

6

2

1

/

2

"

52-160

7

3

52-160

8

3

70-210

9

3

120-350