78

Help Windows

Window text

Help Text

Regulation Mode (Normal Default)

Pumping regulation mode, normal or inverse.
See page 64.

Start Value

Start value, allows pressure to drop in system

PSI or Selected Units

before unit starts. (Disabled is default) See page 64.

Config. 2nd Required Value

Configuration of a second value from another

Off (Default)

sensor. See page 64.

Relay Configuration

Relay configuration. See page 64.

Run Motor (Default)

Submenu

Submenu offset: to enter push “ “ key

Offset

for at least two seconds.

Offset Input

Selection of offset input, if required.

Off (Default)

See page 49.

Level 1

Start level for offset 1.

XX.X %

See page 50.

Level 2

Start level for offset 2.

XX.X%

See page 50.

Intensity 1

Intensity of offset 1.

XX.X%

See page 51.

Intensity 2

Intensity of offset 2.

XX.X%

See page 51.

Submenu

Submenu seq. control; to enter push “ “ key

Seq. Control

for at least two seconds. See pages 52 and 53.

Pressure Incr.

Pressure increment at switching of additional pumps

4 PSI

in multicontroller mode. See pages 52 and 53.

Pressure Dec.

Pressure decrement for consecutive pumps.

4 PSI

See pages 52 and 53.

Enable Seq. Ctl.

Frequency limit enable sequence control. Starts

58 Hz (Default)

second pump in multicontroller. See page 55, step 9.

Switch Interval

Time interval pump sequence change. Allows

12h (Default)

multiple pumps to lead/lag in system, based on
switch interval time. See page 55, step 10.

*

*