Technical characteristics – Xylem IM131R01 AQUAVAR AV II User Manual
Page 87
![background image](/manuals/310496/87/background.png)
Power and Current Ratings
(continued)
Specifications
Environmental MAXIMUM HEATSINK TEMP. = 100º C (212º F)
Operating temperature
0ºC to +40ºC (32ºF to 104ºF) *
Storage temperature
-20ºC to +65ºC (-4ºF to 149ºF)
Humidity
0% to 95% non-condensing
Altitude
1000 m (3300 ft) without derating *
Acoustic noise
80 dBA sound power at 1 m (3 ft)
Electrical
Voltage input
AV2C2x models: 200 to 230 Vac, ±15%
AV2C4x models: 380 to 460 Vac, ±15%
AV2C5x models: 575 Vac, ±15%
Input Line frequency
50 / 60 Hz ±2 Hz
Overvoltage trip
407 Vdc 814 Vdc 1017 Vdc (DC BUS Voltage)
Undervoltage trip
202 Vdc 404 Vdc 505 Vdc (DC BUS Voltage)
Output voltage
0 to 100% of line voltage, 3 Phase
Overload capacity
110% of rated rms for 60 seconds
Rated output frequency
50/60 Hz ±5%
Timed overload
Adjustable time trip set for 110%
of rated motor current
Agency listing
UL and CUL Listed, CE marked
Control Features
Protective features
Overcurrent, overvoltage, phase loss, motor over-
and circuits
temperature, overtemperature, ground fault,
undervoltage, short circuit, sensor fault.
* For high ambient temperatures, derate HP of drive. Altitudes above 3300 ft. of sea level,
derate 2% of HP for every 1000 ft. above 3300 ft. Consult factory for assistance.
Technical Characteristics
86