Technical characteristics – Xylem IM131R01 AQUAVAR AV II User Manual

Page 87

Advertising
background image

Power and Current Ratings

(continued)

Specifications

Environmental MAXIMUM HEATSINK TEMP. = 100º C (212º F)

Operating temperature

0ºC to +40ºC (32ºF to 104ºF) *

Storage temperature

-20ºC to +65ºC (-4ºF to 149ºF)

Humidity

0% to 95% non-condensing

Altitude

1000 m (3300 ft) without derating *

Acoustic noise

80 dBA sound power at 1 m (3 ft)

Electrical

Voltage input

AV2C2x models: 200 to 230 Vac, ±15%
AV2C4x models: 380 to 460 Vac, ±15%
AV2C5x models: 575 Vac, ±15%

Input Line frequency

50 / 60 Hz ±2 Hz

Overvoltage trip

407 Vdc 814 Vdc 1017 Vdc (DC BUS Voltage)

Undervoltage trip

202 Vdc 404 Vdc 505 Vdc (DC BUS Voltage)

Output voltage

0 to 100% of line voltage, 3 Phase

Overload capacity

110% of rated rms for 60 seconds

Rated output frequency

50/60 Hz ±5%

Timed overload

Adjustable time trip set for 110%
of rated motor current

Agency listing

UL and CUL Listed, CE marked

Control Features

Protective features

Overcurrent, overvoltage, phase loss, motor over-

and circuits

temperature, overtemperature, ground fault,
undervoltage, short circuit, sensor fault.

* For high ambient temperatures, derate HP of drive. Altitudes above 3300 ft. of sea level,

derate 2% of HP for every 1000 ft. above 3300 ft. Consult factory for assistance.

Technical Characteristics

86