Entering compensation values, Programming, Instructions – Xylem IM131R01 AQUAVAR AV II User Manual
Page 40: Screen
Entering compensation values:
For steps 1 through 4, refer to the flow chart.
Instructions
1. From the main menu, hold down the
key
for 2-3 seconds until the display changes to:
• Enter 66 by pressing the
2. Freq.- Lifting 30.0 hz This indicates the speed (flow rate)
at which you want the pressure compensation to begin. On a
60 hz system, there is virtually no flow below 40 hz. Set this
frequency with the up arrow. On a 50 hz system, the normal
starting point would be 30 hz.
• Use the
key to scroll through the
menu screens until you reach:
Change if required.
3. Use the
key to move to the next screen:
• Use the
to enter the percentage
pressure increase calculated on page 37.
Increase values are recommended from 0
to 20%. If your friction loss increase is above
20% of your set pressure, please contact the
AQUAVAR distributor or factory for application assistance. 0-99.9% actual.
4. Save the new settings.
• Use the
key to scroll to the screen
• Press both the arrows until the display
indicates the save process is complete.
The screen will automatically return to the main menu.
39
Programming
PASSWORD 0000
0066
Screen
FREQ - LIFTING 40.0 HZ
LIFT - INTENS. 0.0%
LIFT - INTENS. 3.0%
SAVE ??? +
SAVE ??? SAVED
▼
*
*
*
*
▼
▼
▼
▼
▼
▼