AQUAVAR II Controller Program Flow Chart
Single Pump Constant Pressure

II. Single Pump - Pump Protection

The AQUAVARII controller has the ability to protect the pump by shutting it off in low/no suction or run out conditions.

To set run out protection:

For steps 1 through 8, refer to the flow chart on page 36.

Instructions

1. Password The password protection prevents

untrained personnel from accidentally
changing the base settings.

• From the main menu, hold down the

key for 2-3 seconds until the display
changes to:

34

Programming

Diagram 13

FAILURE TO SAVE SETTINGS AFTER PROGRAMMING RESULTS IN LOSS OF
PROGRAM VALUES WHEN POWER IS REMOVED!

WARNING

REQUIRED

VALUE

50 PSI

Auto-START

ON

ERROR 1

ERROR 2

ERROR 3

ERROR 4

ERROR 5

TOTAL RUN

TIME

0000: 41

SAVE ??

– + v

SW Ver.

Date:

ITT Ind.

50 PSI

Press • long

Low/no suction protection can be managed by the installation of a suction line pressure switch,
or float switch for a tank. This switch is connected to the AQUAVAR II controller as described
earlier in the Electrical Installation section. The cut off setting for this switch should be the
maximum NPSH required by the pump.