Object 6030h: Speed Value

This object contains the speed value of the encoder.

Subindex Description

Data Type

Default Value

Access

Restore after

BootUp

0h

Number of sub indices

Unsigned 8

1h

ro

1h

Speed value channel1

Integer 16

-

romap

yes

If the velocity exceeds the data type, the speed value is frozen to the maximal possible value.

The customer can use the 3010h (32 bit) object.

How to map the speed into TPDO2:

(Hint: SDO: 0x600 + Node number. The following values are all in hex and the Nodenumber is "1" DLC

(Data length) = 8 , 22 means "write", This example is written in intel-format (LSB...MSB), depending on

your tool, it could be, that Motorola-format (MSB..LSB) is used and the direction of the Bytes have to be

changed.)

1. The TPDO2 has to be enabled by setting the Transmission type (1801Sub2) to FE:

601 8 22 01 18 02 FE 00 00 00

2. The Event Timer has to be changed from 0x00 to the desired value (e.g.: 100 ms --> 0x64)

601 8 22 01 18 05 64 00 00 00

3. The TPDO mapping Parameter 0 (1A01) has to be dissabled, by setting the Number of entries

(1A01Sub0) to 0:

601 8 22 01 1A 00 00 00 00 00

4. Then the dissabled TPDO mapping Parameter 0 Subindex 1, namely mappedObj1, can be written. The

Speed values is Object 6030Sub1 and the data length is 16Bit --> 10:

601 8 22 01 1A 01 10 01 30 60