BEI Sensors MHK5 Absolute Hollow Shaft Encoder User Manual

Page 70

Advertising
background image

Version 07/10

BEI Sensors CANopen Manual serie M

70

Version history connection cap

In particular the design of the connection cap is

improved. Easier installation due to a new type

of screw terminals inside of the connection cap.

On the back of the connection cap two multi-

color LEDs are implemented for easy diagnosis.

The terminal resistor is hooked up via a slide

switch. Thus continuative bus connection will be

cut off. The localisation of accidentally switched

on terminal resistors wil be made easier. The

device address and the baudrate will be

adjusted via BCD switches. This made the

installation easier.

Changes of the CANopen protocol

The following changes have not be relevant to

you because only specific function according to

the newest CANopen specification (DS-301

V4.0) are not supported anymore or are new

implemented. If your application don’t use this

function, there will be no problem.

Changes of entries in object dictionary

Relevant changes applies to the boot-up

message, as well as some entries in the

CANopen object index not used by the common

user. A complete list of these objects you can

find in the following table.

object-nr.

(hex)

comment CANopen

profile

DS301 V3.0

58XX-XXXX-XBA1C203PG

CANopen profile

DS301 V4.0

58XX-XXXX-XBB1C203PG

1004

Number of PDOs

supported

supported

according to DS301-V4.0 not

supported anymore

100B

Node-ID

supported

according to DS301-V4.0 not

supported anymore

100E COB-ID

Guarding

protocol

supported

according to DS301-V4.0 not

supported anymore

1016 Consumer

heartbeat

time

reserved supported

1017 Producer

heartbeat

time

reserved supported

1018 Identity

Object reserved

supported

Changing transmit PDO communication

parameter

In the new encoder generation the polling isn’t

supported anymore if the PDO is disabled.

According to CANopen specification DS301-

V4.0 it is necessary to set the cyclic time (object

entry [2200h]) to 0 and left the PDO switched on

to poll the encoder. Important! If the PDO is

switched off no communication is possible.

Advertising