BEI Sensors MHK5 Absolute Hollow Shaft Encoder User Manual

Page 71

Advertising
background image

Version 07/10

BEI Sensors CANopen Manual serie M

71

Polling in Pre-Operational state

The old generation has accepted polling

requests in pre-operational state, but wasn’t

correct according to CANopen standard. In the

manual for the old encoder was a hint, that the

polling request is not allowed in pre-operational

state, because it is not defined in the CANopen

standard. So be aware that the new encoder is

in general not accepting poll requests in pre-

operational state independent of configuration of

the behavior as new or old encoder.

Changes in boot-up sequence

If the old encoder generation is connected to the

supply voltage or a NMT message (reset node,

reset communication) is sent to the encoder, a

boot-up message appears. The telegram

structure looks like this: identifier: 80hex + node

number, data length 0 bytes

This message was not defined by the

specification DS301 V3.0, but vendor specific

used by some manufactures to show that the

device is ‘alive’.

According to DS301 V4.0 the new rotary

encoder generation doesn’t support this

message anymore. In place of the old message

a common valid boot-up message is defined.

The structure looks like this:

identifier: 700hex + node number, data length 1

byte

This boot-up message also appears if the

command ‘reset node’ and ‘reset

communication’ is sent to the encoder.

Handling of spare parts

Boot-up message new encoder and old

connection cap

To use the new encoder generation as spare

part for the old encoder generation, the new

encoder recognize the old connection cap type

and support the specification DS301-V3.0

automatically as well as the appropriate boot-up

message.

Changing of the default BootUp message of

the B1 version

To get the same boot-up behavior of the old

encoder generation if you use the new encoder

generation and the new connection cap type

there will be following solution:

The needed protocol type will be activated via a

defined device address. Please use the following

configuration sequence:

1. Setting the needed address (s. table

below).

2. Connect the connection cap to the

encoder.

3. Switch on supply voltage.

4. Wait until both LEDs are red.

5. Switch off supply voltage.

6. Remove connection cap.

7. Set up the correct device address. (0-

89)

8. Connect the connection cap to the

encoder.

9. Switch on supply voltage.

normal operation.

Profile according C2 encoder

protocol DS301-V3.0

protocol DS301-V4.0

address 97

address 98

address 99

Advertising