6. Troubleshooting

6.1 Power on – Encoder doesn’t respond

Problem:

The bus is active but the installed encoder

transmitted no boot up message.

Possible solution:

-

switch of the PLC

-

remove the connection cap of the

encoder

-

check the turn-switch for the baud rate

-

Assemble the connection cap

-

power on

6.2 Malfunction of the position value during

transmission

Problem:

During the transmission of the position value

occasional malfunction occurs. The CAN bus can

be temporary in the bus off state also.

Possible solution:

Check, if the last bus node has switched on the

terminal resistor. If the last bus node is an encoder

the terminal resistor is situated in the connection

cap.

6.3 Too much ERROR-Frames

Problem:

The bus load is too high in case of too much error

frames.

Possible solution:

Check if all bus node has the same baud rate. If

one node has another baud rate error frames are

produced automatically.

6.4 Limit switches without function

Problem:

The encoder didn’t transmit the bits for the limit

switches.

Possible solution:

The limit switch functionality has to be activated

once. Please follow the description you can find at

4.5.

6.5 Encoder without connection cap

Notice: The changing of baud rate and node

number are only valid after a new power up, NMT

Reset or the store parameters command.