BEI Sensors MHK5 Absolute Hollow Shaft Encoder User Manual

Page 69

Advertising
background image

Version 07/10

BEI Sensors CANopen Manual serie M

69

 Singleturn

10196h

 Mutliturn

20196h

3.5 Restore Command

In the past the restore command set the encoder

to customised default values The restore

command sets the encoder to BEI Sensors

default values, which are defined in the user

manual. Communication parameters like node

number and baud rate are not restored.

3.6 Connection Cap BCD-switch setting “9”

The, former undefined, BCD-switch setting “9” in

the connection cap is used to set the encoder in

a mode, that ignores the switch setting for baud

rate and node number. The parameters can be

modified by SDO messages and LSS, only.

3.7 C2-C5-Work-around

With little limitations, the new encoder line will be

compatible to the current version. It will be

possible to use the old EDS-file for configuration

purposes in the PLC with the new encoder and

no errors will occur. Merely the enhanced

functions, like velocity- and acceleration-output,

will not be available.

In case for unexpected problems, there is the

possibility to set the CA-encoder in a

compatibility mode, that will restore the old C2-

C5-behavior.

There are the following procedures to set this

mode:

 Manual, with the BCD-switch in the

connection cap:

o

Remove cap from encoder

o

Set node number 97

o

Reconnect connection cap 

Both LEDs will glow in red.

o

Remove connection cap again

and set back to the needed
node number

o

Reconnect connection cap 

C2-C5-Behavior

 Via

Software:

o

Set object 3030h subindex 1h

to „ONE“ via SDO-commando

o

Hard- or Software RESET

CA00

Type key

Nr. type key old

type key new

comment

1

2

58XX-XXXX-XBA1C203PG

AH58-CA-3PG

58XX-XXXX-XBB1C203PG

AH58-B1CA-3PG

encoder CAN

connection cap CAN

X: wildcard for various designs

Advertising
This manual is related to the following products: