7.20 Slug detection (detailed Setup)

Slug detection

Not available if gas measurement
is ordered.

Detection of bubble flow.

After slug criteria has been reached, slug is supervised during slug
duration. If slug is still detected after slug duration has expired, the
selected action in

After slug is taken.

See below table.

Slug alarm select

Select:

Not apply, Apply

drive gain

To read drive gain.
To set a suitable slug criteria the customer must know the drive gain
level of normal flow condition and of slug flow condition. This function is
suitable to evaluate this level.

Slug criteria

Above this drive gain level slug flow is assumed.

Slug duration

Duration time is designed to ignore short gas bubbles. Only after Slug
duration has expired the setting in After slug will be taken in account.
In normal slug application set slug duration to zero.

After slug

Select:

Measured value, Hold

If

Hold is selected mass flow and density keep their value before

occurrence of the slug alarm and as long as slug alarm is detected.

drive gain damping

Set drive gain damping time to get a constant drive gain level.

Gas application?

Yes

No

Slug detection off

Slug alarm select = Apply?

Yes

No

Drive gain > Slug criteria?

Slug detection off

Yes

No

Duration active?

Yes

After duration

Function active

Alarm off

Measurement

continued

Slug detection On

Alarm on

Measurement

continued

or value hold

Slug detection off

Alarm off

time

mass flow

drive gain

density

single
bubble

slug flow

duration time

mass flow, if

Hold

mass flow, if

Measured value

T88.EPS

Influence of slug on mass flow, density and drive gain :