7. pArAMETEr dESCrIpTION

7-9

IM 01R04B04-00E-E 8th edition March 01, 2011 -00

All Rights Reserved. Copyright © 2003, Rota Yokogawa

parameter

data
form

data range

dec.

point

Unit

r : read
W : write
Exe :
execute

reset

Master

reset

power on

default

Temperature format

Select

xxxxxxx

-

-

R/W

X

xxxxxx.X

xxxxx.X

xxxx.XX

xxx.XXX

xx.XXXX

x.XXXXX

Temperature LRV

Decimal

Standard: -200 to 230°C 0 to 5

Temperature unit

R/W

X

-200

High Temp.: 0 to 400°C

Temperature URV

Decimal

Standard: -200 to 230°C 0 to 5

Temperature unit

R/W

X

230

High Temp.: 0 to 400°C

Temperature damping

Decimal

0 to 200

1

Sec.

R/W

X

3

Temp alm 1 sel

Select

No function

-

-

R/W

X

No function

More than

Less than

Temp alm 1 crit

Decimal

Standard: -200 to 200°C 0 to 5

Temperature unit

R/W

X

LRV

Temp alm 2 sel

Select

No function

-

-

R/W

X

No function

More than

Less than

Temp alm 2 crit

Decimal

Standard: -200 to 230°C 0 to 5

Temperature unit

R/W

X

URV

High Temp.: 0 to 400°C

Temp fix val select

Select

Inhibit

-

-

R/W

X

X

Inhibit

Enable

Temp fixed val

Decimal

Standard: -200 to 230°C 1

Temperature unit

R/W

X

X

30

High Temp.: 0 to 400°C

Temp gain

Decimal

0.8 to 1.2

3

-

R/W

1

Velocity unit

Select

m/s

-

-

R/W

X

m/s

ft/s

Analog 1 select

Select

Mass flow

-

-

R/W

X

Mass flow

Volume flow

Density

Temperature

Concentration meas

Net flow

None

Analog 1 alarm out

Select

<2.4mA

-

-

R/W

X

<3.6mA

<3.6mA

4.0mA

>21mA

>21.6mA

Hold

Measured Value

Analog 1 low LMT

Decimal

NAMUR:3.8 to 20.5 mA 2

mA

R/W

X

3.8 (Namur);

Not NAMUR:2.4 to
21.6 mA

2.4 (not
Namur)

Analog 1 high LMT

Decimal

NAMUR:3.8 to 20.5 mA 2

mA

R/W

X

20.5 (Namur);

Not NAMUR:2.4 to
21.6 mA

21.6 (not
Namur)