A2 SAFETY INSTrUMENTEd SYSTEMS INSTAllATION

A2-1

IM 01R04B04-00E-E 8th edition March 01, 2011 -00

All Rights Reserved. Copyright © 2003, Rota Yokogawa

AppENdIX 2. Safety Instrumented

Systems Installation

The contents of this appendix are cited from exida.com safety manual on the Rotamass 3 series Coriolis Mass

Flow and Density meter specifically observed for the safety transmitter purpose. When using the Rotamass 3

for Safety Instrumented Systems (SIS) application, the instructions and procedures in this section must be

strictly followed in order to preserve the transmitter for that safety level.

A2.1 Scope and purpose

This document provides an overview of the user responsibilities for installation and operation of the
Yokogawa ROTAMASS 3 Series Coriolis Mass Flow and Density Meter in order to maintain the designed
safety level. Items that will be addressed are proof testing, repair and replacement of the flowmeter, reliability
data, lifetime, environmental and application limits, and parameter settings.

A2.2 Using rotamass 3 for a SIS Application

A2.2.1 Safety Function

This flowmeter is intended for use as a mass flow, fluid density and fluid temperature measurement
component in a Safety Instrumented System. It has two 4-20 mA analog outputs, two passive pulse outputs/
status outputs and one status input. The flowmeter may be used with the two 4 – 20 mA outputs to feed
signals to a logic solver that is part of the safety instrumented function (SIF) as shown in Figure A2-1. The
fault annunciation mechanism is an out of range analog current. In order to take credit for the automatic
diagnostics in the flowmeter, this annunciation mechanism must be connected.

Figure A2-1 Example Safety Instrumented Function