9. EXplOSION prOTECTEd TYpE INSTrUMENTS

9-12

All Rights Reserved. Copyright © 2003, Rota Yokogawa

IM 01R04B04-00E-E 8th edition March 01, 2011 -00

9.2.3 general warnings

- Substitution of components may impair intrinsic safety !
- Only trained persons may use the instrument in industrial location.
- The instrument modification of parts replacement by other than authorized representatives of YOKOGAWA

is prohibited and will void the certification.

- If the cover of the converter case has to be opened, following instructions must be followed:

- Confirm that the power cables to the instrument are disconnected.

- Wait 15 minutes after power is turned off before opening the covers.

- The covers of display side and terminal box are fixed with special screws,

please use Hexagonal Wrench to open the covers.

- Be sure to lock the cover with special screw using the Hexagonal Wrench after

tightening the cover (see drawing chapter 4.3).

- Prohibition of specification changes and modifications. Users are prohibited from

making any modifications of specifications or physical configuration, such as adding or changing the

configuration of external wiring ports.

WARNING

remote rack-mount type rCCr31 with rCCS3

1.

Remote rack-mount converter RCCR31 must only be installed in safe area !

2.

Ex-type RCCR31 and RCCS3 must be connected to the suitable IS earthing system

(see installation diagram). Converter and detector case must have connection to he potential

equalisation facility.

3.

Please confirm that the ground terminal on terminal board is firmly connected.

4.

For EMC technical reasons the case of the detector is connected to the case of the

converter via the shielding of the interconnecting cable.

Installation diagram :

L/+

N/-

G

Power supply

I/O control

Hazardous area

Safe area

I/O

RCCR31

RCCS3

D+
D-
S1+

S1-

S2+

S2-

TP1

TP2

TP3

D+
D-
S1+

S1-

S2+

S2-

TP1

TP2

TP3
COM

Exclusive remote cable RCCY03

F93.EPS

Terminal Board

WARNING