9. EXplOSION prOTECTEd TYpE INSTrUMENTS

9-23

All Rights Reserved. Copyright © 2003, Rota Yokogawa

IM 01R04B04-00E-E 8th edition March 01, 2011 -00

remote rack-mount type rCCr31 with rCCS3

WARNING

1. Remote rack mount converter RCCR31 must only be installed in safe area !
2. Ex-type RCCR31 and RCCS3 must be connected to the suitable IS earthing system (see installation
diagram). Converter and detector case must have connection to the potential equalisation facility.
3. Please confirm that the ground terminal on terminal board is firmly connected.
4. Ex-e terminals for power supply and I/O-lines are designed for cables with cross section of 0.08 mm²
(AWG 28) to 2.5 mm² (AWG 22). The strip length must be 5 to 6 mm (0.2 to 0.24 in).
5. For EMC technical reasons the case of the detector is connected to the case of the converter via the
shielding of the interconnecting cable.

Installation diagram :

L/+

N/-

G

Power supply

I/O control

Hazardous area

Safe area

I/O

RCCR31

RCCS3

D+
D-
S1+

S1-

S2+

S2-

TP1

TP2

TP3

D+
D-
S1+

S1-

S2+

S2-

TP1

TP2

TP3
COM

Exclusive remote cable RCCY03

F93.EPS

Terminal Board

L/+

N/-

G

Power supply

I/O control

Hazardous area

Safe area

I/O

RCCF31

RCCS3

D+
D-
S1+

S1-

S2+

S2-

TP1

TP2

TP3

D+
D-
S1+

S1-

S2+

S2-

TP1

TP2

TP3
COM

Exclusive remote cable RCCY03

F92.EPS

Terminal Box

The inner shields (shields of the cable pairs) are connected together to COM –terminal on converter side.
The outer shield of the cable is connected on both sides to the cases by cable gland.

Detailed information for connection intrinsic safe outputs (option /EF2) see chapter 4.8.8.

Installation diagram (option /EF1) :